135
Informasi Produk

Spesifikasi Smoke Detector

Voltage Range
15 - 32 volts DC peak
Standby Current
Ion/Thermal:
150 uA @ 24 VDC (without communication, LED off)
200 uA @ 24 VDC (one communication every 5 sec. with LED enabled)
Photo/Photo with Thermal:
250 uA @ 24 VDC (without communication, LED off)
300 uA @ 24 VDC (one communication every 5 sec. with LED enabled)
Pinnacle:
230 μA @ 24VDC (without communication)
330 μA @ 24VDC (one communication every 5 sec. with LED enabled)
LED Current (max.)
6.5 mA @ 24 VDC (on)
Height
2.0 inches (51 mm)
1.66 inches (42 mm) - Pinnacle
Diameter
6.1 inches (155 mm) Installed in B210LP Base
4.1 inches (104 mm) Installed in B501 Base
4.0 inches (102 mm) - Pinnacle
Shipping Weight
Heat: 4.8 oz. (137 g)
Photo/Photo with Heat: 5.2 oz. (147 g)
Ion: 5.4 oz. (154 g)
Pinnacle: 5.6ox. (159 g)
Relative Humidity
10% - 93% noncondensing

Smoke Detector Secutron Addressable INDMRI-2251B

Features
• Sleek, low profie design
• Detectors are equipped with a built-in analog communications module
• Smoke detectors are available with photoelectric or ionization technology
• Photoelectric detectors are available with additional fied temperature detection
• Heat detectors are available as fied temperature or fied temperature with rate-of-rise detection
• Dual LEDs indicate communications and activate steady when in alarm
• Low profie base provides easy interchangeability
• Low standby current
• Rotary address switches
• Magnetic test feature
• Superior EMI protection
• Sealed against dirt, insects, and back pressure

Smoke Detector Konvensional SD-2WP-LED

Smoke Sensitivity 2.66+/- 1.11% FT Obscuration (UL standard)
Detection Range 50 foot rating for heat sensor
Start-Up Current 70 μA Maximum
Alarm Impedance For 2-wire models: 100Ω+3V max; 560Ω+3V max (red LED open circuit)
Reset Voltage Less than 1 volt
Reset Time Less than 1 sec
Alarm Indicator Continuously emitting red light
Temperature range -10°C to 50°C
Humidity 0 to 95% RH, non condensing
Alarm Contact For 4-wire: N/O or N/C Operation
Form A: 1.0A@30VDC/0.5A@125VAC
Dimensions 10mm (dia) x 46mm (ht) with base
Weight 130g/set with base

Features
• Two and four wire models
• Photoelectric smoke sensing technology
• Uses smoke sensor in conjunction with a fixed
temperature heat sensor to extend reliability
• Durable sensor head, no need for replacement
• N/C (normal close) or N/O (normal open) selectable
relay output
• Easy installation and maintenance
• Attractive sleek housing
• UL listed

Fungsi Smoke Detector

Smoke Detector Secutron akan mendeteksi asap kebakaran dengan baik. Perangkat ini akan memberikan input berupa sinyal elektrik yang akan diteruskan ke panel kontrol. Dari panel kontrol, sistem akan aktif sehingga dapat memperingatkan para penghuni gedung untuk segera mengambil tindakan pemadaman atau melakukan evakuasi, baik barang maupun diri. Fire alarm akan membantu melakukan identifikasi kebakaran sejak dini, baik melalui detektor asap atau panas.